Shanghai Kehua Thermal Pipe Co., Ltd.

Leak Detection: Principles and Deployment

· Technical Notes

Embedded sensor wires locate leaks by detecting impedance changes when insulation absorbs moisture.

During deployment, wire splicing and joint sealing quality are critical — most false alarms come from wet joints rather than pipe leakage.

Baseline impedance calibration at acceptance provides the reference for future comparison.